Oldham Simtronics OLCT 80 Fixed Gas Detector

SKU: OLCT-80
Manufacturer:
Oldham Simtronics

Bulk Orders

Competitive Pricing
Short Lead Times
Consolidated Shipping
Prompt Response
Request a Quote

Features

  • Detectors-Transmitters for Flammable, Toxic Gases and Oxygen
  • Non-intrusive operation via intrinsically safe infrared remote control
  • Remote versions available XP, IS
  • Integrated relays
  • Direct link, 4-20 mA, loop and isolated sensor mode

Unique advantages providing the solution you need

Design advantages

Pre-calibrated sensors for detection of:

  • combustible gases: LEL catalytic and IR
  • toxic gases
  • oxygen

Alarms

  • 2 integrated gas alarms with relays
  • 1 fault alarm with relay

Inputs

Series 80 sensors have up to 9 glands dedicated to cable wiring Design advantages:
The minimum configuration includes:

  • 1 electrical input dedicated to a sensor.
  • two 4-20 mA or binary inputs. This configuration allows any other sensor from the network to be recognized (e.g temperature sensor, emergency stop, flame detector, smoke detector).

Outputs

  • 4/20 mA with smart signal processing
  • analog signal 4-20 mA
  • data signals between 0 and 4 – 20 and 25mA

The transmitted signal, between 0 and 3.2 mA and above 20 mA, can be processed to interpret and identify a wide range of trouble parameters such as: line faults, sensor faults, embedded electronics faults, ambiguity resolution, inhibition of calibration, maintenance call (initial drift or drift over time).

  • RS485 (1200 bauds, 38kb Modbus ASCII for MX 62).

The RS485 link gives access to :
– sensor measurement
– status and default
– internal relay management

Relays

The relays are 2A / 250 VAC type with potential free SPDT contacts.

Two types of relays:

  • 2 gas alarm relays or supplementary inputs
  • 1 fault relay

The relays are actuated either

  • directly by the sensor electronics or supplementary
    inputs, or
  • from the MX62 central unit or the control system to which the sensor is connected.

The relays can be

  • in safety mode or not,
  • triggered on increasing or decreasing alarms,
  • manually* or automatically acknowledged.
  • * By remote control, by pressing an external pushbutton connected to the dedicated binary input, by acknowledging on the MX 62 unit or the control system to which the sensor is connected.

Alarms

  • 2 integrated gas alarms with relays
  • 1 fault alarm with relay

Technical advantages

Stand-alone central unit
For relay control, the OLCT 80 can operate as a standalone unit: an indisputable advantage in a classified explosion risk zone.

Flexibility of connection modes
OLCT 80 sensors can be connected either:

  • in loop (opto-isolated – up to 16 sensors),
  • 4-20 mA,
  • under direct power and operate as a central unit.

Operation traceability
The operator can check records locally for the most recent time-date stamped events.

Communication
Remote dialogue with the sensor using IR remote control.

Measurement power supply redundancy
Independent ports allow a redundant connection to the measurement unit.

Low power requirements
The leading edge technology used in the OLCT80 transmitter makes it very energy efficient. This major advantage means that more sensors can be connected, with smaller wire cross-sections and over greater distances.

Logistic advantages

Loop arrangement
The transmitter is perfectly adapted to mounting and connection to the digital fieldbus loop of the MX 62 unit. Supporting 1 to 3 digital addresses:

  • the sensor block (detection element),
  • the two 4-20 mA auxiliary inputs.

Certification

The OLCT80 Series is certified to the specifications required by standards EN 50054, 45544 and 50104 (environmental standards, explosive and toxic gases and oxygen) and to the specifications of standards EN 50270, EN 6052 (electromagnetic compatibility, ingress protection).

OLCT 80 uses digital logic and software technologies.
The sensors are protected and in compliance with the specifications of standard EN 51271:

  • analog and digital values track each other
  • homogeneity of digital resolution and response time with the specifications required
  • internal self-diagnostics

OLCT 80

Configuration Options

Configuration Options
Stand Alone Version
Configuration Options
Standard Version
Configuration Options
Stand Alone Version
Digital Version


Specifications

Type Transmitter-sensor
Detected gases Explosive, toxic and oxygen
Detection principles Catalytic, Electrochemical, IR, Semiconductor
Sensor block Pre-calibrated
Device Aluminium enclosure and stainless steel 316Lfor sensor housing
Visualisation 4-digit LCD display for measurement
and one alphanumeric line for texts,
Pictograms – backlighting
4 indicator lamps : one green : “OperationOK”, one yellow : “Fault”, red : “Alarm 1” and “Alarm 2”
Power supply From 16 to 28 VDC at transmitter entry
Maximum power with digital link
– 0.2 W (electrochemical cell) – 1.3 W ( catalytic / SM )
with I output at 25 mA
– 0.9 W (electrochemical cell) – 2 W ( catalytic / SM )
with I output at 25 mA and relays activated
– 2.4 W (electrochemical cell) – 3.5 W ( catalytic / SM )
Power supply to
sensor terminals
Two independent inputs :
16 to 28 VDC (catalytic / IR / SM cells)
12 to 28 VDC (electrochemical cell)
Inputs Two analog inputs 4-20 mA (load resistance 120 Ω, can be used as binary)


Signal outputs

Logic (relay contacts) Relay
Analog Standardised 4-20 mA output
Digital Two independent opto-isolated RS 485 ports
Signal faults I < 0.5 mA
Alarms 2 programmable thresholds per channel


Relays

Type SPDT
Number 3
Contact RCT changer-over
Breaking capacity 2A / 250 VAC / 30 VDC
Wiring / connection Basic version, 6 inputs : 4 M20 and 2 M25
On request : 3 additional, 2 M20 and 1 M25
Load resistance
on the 4-20 mA
500 Ω
Loop resistance Under central unit 21 VDC: 128 ohms ( electrochemical cell ) – 32 Ω ( catalytic / SM ) – 16 Ω (IR)
Protection number IP 66
Operating temperatures – 20 °C to + 60 °C ( electronics, see table for detection cells )
Dimensions See drawings
Weight OLCT 80 : 3,5 kg,        OLCT80 version IR : 5,3 kg

 

Oldham Simtronics OLCT 80 Fixed Gas Detector

Accessories

OLCT 80 Accessories

A Infrared remote control
B Tool kit
C Bypass adapter
D Cover key
E Calibration cup
F Remote gas introduction device
G Gas collector
H Splash guard


Homologations

Certification Atex
OLCT 80 d OLCT 80 id
ATEX II 2GD ATEX II 2GD
Ex d IIC T6…T5 Gb Ex d ia IIC T4 Gb
Ex tb IIIC T85°C…T100°C Db Ex tb ia IIIC T135°C Db
INERIS 03ATEX0240X INERIS 03ATEX0240X
Chine
OLCT 80 d OLCT 80 id
GYJ17.1201X – Ex d IIC T6/T5 Gb GYJ17.1202X – Ex d ia IIC T4 Gb
Electromagnetic compatibility
Complies with EN 50270

 

Product Data Sheet