EQ3710 AIM Analog Input Module (Spec Sheet: 90-1183). The 8 Channel Analog Input Module expands the input capability of the Det-Tronics Eagle Quantum Premier System. The unit provides a means of connecting devices with a 4-20 mA output signal to the Eagle Quantum Premier System.
Each channel is fully configurable to provide device and alarm information. This information includes tag name, descriptor, engineering units, fault alarm, low/high alarm, and alarm threshold limits.
- Compliance to ANSI/ISA-12.13.01, for combustible gas
- Compliance to ANSI/ISA 92.0.01, CSA 22.2 #152, and EN60079-29-1
- NFPA 72 Approved 4-20 mA flame detector input
- Class 1 Div. 2 locations combined with Zone 2 rated devices Type N
- Models with SIL 2 certification
- Monitors eight independent channels
- Panel or DIN rail mounting
- Optional HART Interface module (HIM) available
- Supports 2 or 3 wire 4-20 mA transmitters
EQ3710 AIM Model Matrix
MODEL | DESCRIPTION |
EQ3710 | 8 Channel Analog Input Module (AIM) |
TYPE | MOUNTING OPTION |
D | Din Rail |
P | Panel |
TYPE | APPROVALS |
R | VNIIPO/VNIIFTRI (RUSSIA) |
S | SIL |
T | SIL/FM/CSA/ATEX/IECEx |
W | FM/CSA/ATEX/IECEx |
*Type Approvals can use one or more letters to designate the approvals of the product.
EQ3710 AIM – SIL 2
Model | Part Number | Material | SIL/FM/CSA/ ATEX/IECEx |
Ship Weight |
EQ3710DT | 007918-013 | AL | X | 2.0 lb (0.90 kg) |
EQ3710PT | 007918-012 | AL | X | 1.0 lb (0.45 kg) |
EQ3710 AIM
Model | Part Number | Material | FM/CSA/ ATEX/IECEx |
Ship Weight |
EQ3710DW | 007918-003 | AL | X | 2.0 lb (0.90 kg) |
EQ3710PW | 007918-002 | AL | X | 1.0 lb (0.45 kg) |
Be the first to review “Det-Tronics EQ3710 AIM Analog Input Module” Cancel reply
Related products
-
Spectrex 20/20MPI Commercial IR3 Flame Detector
With its lightweight housing and low power consumption, the 20/20MPI provides a cost effective solution, specially suited to indoor applications such as transport terminals, storage areas, industrial kitchens and historical and cultural sites with large open areas, providing an efficient alternative smoke and heat detectors often prove to be ineffective. The 20/20MPI is a compact, lightweight, high performance IR3 detector with a new design for retail use based on industrially proven IR3 technology. The 20/20MPI retains all the benefits of IR3 technology, including long distance detection and the highest immunity to false alarms. Main Features Long distance Flame Detection (up to 140ft / 43m) Large Field of View (100° horizontal / 90° vertical) Highest immunity to false alarms Output options (two models): – Alarm and Fault relay outputs (4 wire) or – Stepped mA output (3 wire source) RS-485 Modbus Compatible Automatic and Manual Built-In-Test (BIT) 3 Year Warranty Applications AIRPORT TERMINALS Airport terminals situated in dense cities often have large halls, accompanied by retail, food and beverage outlets, each with their fire risks, which don’t have full fire protection coverage. With the structure’s size and complex design, fires are often difficult to detect and larger fires are less common due to the large air intake. TRAIN STATIONS AND TERMINALS Train stations and terminals often have large atria containing food and beverage outlets which have large air intake and often have little fire protection coverage. Additionally, within these areas, electricity and fuel are present, increasing the chances of ignition. STORAGE AREAS A wide range of substances are stored within open or closed storage facilities, part of which can be dangerous or flammable, creating a greater fire hazard than usual. ARCHIVES A large amount of paper work collecting dust poses potential fire hazards that require monitoring. MALLS With over 1,000 fire events taking place annually within the retail industry, it is imperative that the large open areas with high ceilings found in shopping malls have full fire protection coverage in order to avoid damage to assets and personnel. HOSPITALS Hospitals consist of large open spaces and confined rooms, all of which contain a wide variety of contents that pose hazards. Cooking and heating equipment, as well as electrical distribution, lighting and medical equipment such as oxygen tanks are found throughout hospital buildings and are all potential fire risks which should be protected against. CAR PARKING TOWERS AND GARAGES Areas intended for vehicle storage or maintenance contain large amounts of fuel and fumes within an enclosed space, posing a fire hazard that must be monitored. PUBLIC BUILDINGS Public buildings often house governmental offices and more, requiring excellent fire protection in order to prevent damage to assets and personnel in any potential fire. BANKS AND OFFICES Banks and offices face common fire hazards with large open areas, coupled with large amounts of paperwork and a large volume of people constantly passing through. HISTORICAL AND CULTURAL SITES Historical, cultural or national sites often contain irreplaceable assets, alongside flammable materials. A fire within these areas which were not designed with safety in mind would cause irreversible damage. AIRCRAFT HANGARS Large open floor areas with high roofs provide a suitable area for aircraft storage and repair. However, the large quantities of liquid jet fuel and risk of spill, coupled with maintenance activities provide potential ignition sources which is complicated by aircraft wing obstructions. CABLE TUNNELS Cable tunnels play an essential role in every industrial company. Any fire damage to the cables puts entire production areas out of action. As the cable tunnel environment deteriorates with time, cable insulation performance decreases, leaving an increased heating value and greater risk of tunnel fires and detection of these fires is essential in order to prevent further damage. Product Data Sheet -
Det-Tronics X2200 UV Flame Detector
X2200 UV Flame Detector (Spec Sheet: 90-1157) meets the most stringent requirements worldwide with advanced signal processing and immunity to extraneous sources, combined with Ultra-high speed capability. The detector is equipped with both automatic and manual oi (optical integrity). The detector has Division and Zone explosion-proof ratings and is suitable for use in a variety of applications. The standard output configuration includes fire, fault, and auxiliary relays with RS-485 Modbus. Optional 0-20 mA, Pulse, Eagle Quantum Premier, or HART outputs are also available. A model with pulse output is available for easy retrofitting into existing Det-Tronics R74XX controller based systems. The X2200 housing is available in aluminum or stainless steel, with NEMA/Type 4X and IP66/IP67 rating. Typical applications include: HVDC converter stations, munitions, sulfur production, and silane storage. Models available with SIL 2 certification ARC rejection - Advanced signal processing Unequaled false alarm rejection - Solar blind Responds to a fire in the presence of modulated blackbody radiation without false alarm Ultra-High speed capability Optional HART output and AMS aware Automatic, manual, or magnetic oi (optical integrity) testing Pulse output for compatibility with Det-Tronics R74XX controller-based systems (optional) FM, CSA, ATEX, CE, and IECEx EN 54 part 10 certified by BRE, LPCB Tricolor LED indicates normal operation, fire, and fault conditions Mounting arm allows easy sighting Integral wiring compartment for ease of installation Terminal block allows for Class X Pathway Designation per NFPA 72 EMI, RFI, EMC Directive Compliant Built-in data logging / event monitoring Models available with integral Explosion-proof camera option (xWatch) Molybdenum Model available for applications that require increased spectral sensitivity X2200 Model Matrix MODEL DESCRIPTION X2200 UV Flame Detector X2200G UV Flame Detector with Kr85 free Source Tube X2200M* UV Flame Detector with Molybdenum Tube X2200GM* UV Flame Detector with Molybdenum Tube, Kr85 free TYPE MATERIAL A Aluminum (AL) S Stainless Steel (SS) TYPE THREAD TYPE 3M 3 Port, M25† 3N 3 Port, 3/4" NPT† 4M 4 Port, M25 4N 4 Port, 3/4" NPT TYPE OUTPUTS 11 Relay 13 Relay and 0-20 mA 14 Eagle Quantum Premier 15 Relay and Pulse 16 Addressable Module Only (third-party type) 23‡ HART, Relay, and 0-20 mA 24 Eagle Quantum 33 Relay and 0-20 mA / NTSC (xWatch) 34 Eagle Quantum Premier / NTSC (xWatch) 43 Relay and 0-20 mA / PAL (xWatch) 44 Eagle Quantum Premier / PAL (xWatch) TYPE APPROVALS§ A FM/CSA B INMETRO (BRAZIL) E ATEX/IECEx/EN 54-10 R VNIIPO/VNIIFTRI (RUSSIA) S SIL T SIL/FM/CSA/ATEX/IECEx U TCCExEE/UKRCEPRO (UKRAINE) W FM/CSA/ATEX/IECEx TYPE CLASSIFICATION 1 Division/Zone Ex d e 2 Division/Zone Ex d *Special Application - consult factory before ordering. †3 port models are only available with output types 33, 34, 43, and 44 (xWatch) ‡Type 23 Output - When HART output chosen detector does not have RS-485 communication available. §Type Approvals can use one or more letters to designate the approvals of the product Table D1 - X2200 Software Part Number Configuration Matrix Dash UV Sensitivity Arc Rejection Alarm Relay Aux Output Function Aux Relay Fault Relay -001 High High De-Energized Non-latching Follows Alarm Energized Non-latching Energized Non-latching -002 High Very High De-Energized Non-latching Follows Alarm Energized Non-latching Energized Non-latching -003 High Off De-Energized Non-latching Pre-Alarm Energized Non-latching Energized Non-latching -005 Medium High De-Energized Non-latching Follows Alarm Energized Non-latching Energized Non-latching -006 High High De-Energized Non-latching Pre-Alarm Energized Non-latching Energized Non-latching -007 High High De-Energized Latching Follows Alarm De-energized Latching Energized Non-latching -008 High Very High De-Energized Latching Follows Alarm De-energized Latching Energized Non-latching -009 High Off De-Energized Latching Pre-Alarm De-energized Latching Energized Non-latching -010 Medium High De-Energized Latching Follows Alarm De-energized Latching Energized Non-latching -011 High High De-Energized Latching Pre-Alarm De-energized Latching Energized Non-latching -013* High Off De-Energized Non-latching Follows Alarm Energized Non-latching Energized Non-latching -014* High Off De-Energized Latching Follows Alarm De-Energized Non-latching Energized Non-latching -015 Very High Low De-Energized Non-latching Follows Alarm Energized Non-latching Energized Non-latching -016 Very High Low De-Energized Latching Follows Alarm De-Energized Non-latching Energized Non-latching -017 Very High Off De-Energized Non-latching Pre-Alarm Energized Non-latching Energized Non-latching -018 Very High Off De-Energized Non-latching Follows Alarm Energized Non-latching Energized Non-latching -019 Very High Off De-Energized Non-latching Pre-Alarm De-Energized Non-latching Energized Non-latching *Available only on the X2200M model ARC = Arc Rejection. An algorithm that prevents false alarms from transient UV sources Application Guidelines The following criteria should be considered when choosing a sensitivity level for the intended application: Speed of response based on fuel type and fire size Distance between the hazard and the flame detector These are typical industry application settings. They may not be applicable to all installations. Contact factory for additional application guidance. HVDC 019 Compressor 002 High Speed 003 Automotive 005 Turbine 006 Munitions 013/019 NOTE: Latching relays cannot be used in voted systems. X2200 UV Flame Detector - SIL 2 Model Part Number * Material Threads Output Div/Zone Ex d e Div/Zone SIL/FM/CSA/ ATEX/IECEx X2200A4N13T1 008430-XXX AL 3/4 NPT Relay/0-20 mA X X X2200A4M13T1 008431-XXX AL M25 Relay/0-20 mA X X X2200S4N13T1 008432-XXX SS 3/4 NPT Relay/0-20 mA X X X2200S4M13T1 008433-XXX SS M25 Relay/0-20 mA X X X2200A4N13T2 008434-XXX AL 3/4 NPT Relay/0-20 mA X X X2200A4M13T2 008435-XXX AL M25 Relay/0-20 mA X X X2200S4N13T2 008436-XXX SS 3/4 NPT Relay/0-20 mA X X X2200S4M13T2 008437-XXX SS M25 Relay/0-20 mA X X X2200A4N23T1 008438-XXX AL 3/4 NPT Rly/0-20/HART X X X2200A4M23T1 008439-XXX AL M25 Rly/0-20/HART X X X2200S4N23T1 008440-XXX SS 3/4 NPT Rly/0-20/HART X X X2200S4M23T1 008441-XXX SS M25 Rly/0-20/HART X X X2200A4N23T2 008442-XXX AL 3/4 NPT Rly/0-20/HART X X X2200A4M23T2 008443-XXX AL M25 Rly/0-20/HART X X X2200S4N23T2 008444-XXX SS 3/4 NPT Rly/0-20/HART X X X2200S4M23T2 008445-XXX SS M25 Rly/0-20/HART X X Ship Weight: Aluminum = 7lb (3.2kg) Stainless Steel = 14.6lb (6.7kg) *The last 3 digits of the part number identify the software configuration. Please see table D1 to choose the correct option. X2200 UV Flame Detector - Moly - SIL 2 The X2200M UV detector utilizes a molybdenum (moly) sensing element. Moly-based sensors have an increased spectral range of 1850 to 2650 angstroms, which is better suited for detecting substances with unusual chemistry, sulfur fires, and some black powders. Model Part Number * Material Threads Output Div/Zone Ex d e Div/Zone Ex d SIL/FM/CSA/ ATEX/IECEx X2200MA4N23T1 008446-XXX AL 3/4 NPT Rly/0-20/HART X X X2200MA4M23T1 008447-XXX AL M25 Rly/0-20/HART X X X2200MS4N23T1 008448-XXX SS 3/4 NPT Rly/0-20/HART X X X2200MS4M23T1 008449-XXX SS M25 Rly/0-20/HART X X X2200MA4N23T2 008450-XXX AL 3/4 NPT Rly/0-20/HART X X X2200MA4M23T2 008451-XXX AL M25 Rly/0-20/HART X X X2200MS4N23T2 008452-XXX SS 3/4 NPT Rly/0-20/HART X X X2200MS4M23T2 008453-XXX SS M25 Rly/0-20/HART X X Ship Weight: Aluminum = 7lb (3.2kg) Stainless Steel = 14.6lb (6.7kg) X2200 UV Flame Detector Model Part Number * Material Threads Output Div/Zone Ex d e Div/Zone Ex d FM/CSA/ ATEX/IECEx X2200A4N11W1 008300-XXX AL 3/4 NPT Relay X X X2200A4M11W1 008301-XXX AL M25 Relay X X X2200S4N11W1 008302-XXX SS 3/4 NPT Relay X X X2200S4M11W1 008303-XXX SS M25 Relay X X X2200A4N11W2 008304-XXX AL 3/4 NPT Relay X X X2200A4M11W2 008305-XXX AL M25 Relay X X X2200S4N11W2 008306-XXX SS 3/4 NPT Relay X X X2200S4M11W2 008307-XXX SS M25 Relay X X X2200A4N14W1 008316-001 AL 3/4 NPT EQP X X X2200A4M14W1 008317-001 AL M25 EQP X X X2200S4N14W1 008318-001 SS 3/4 NPT EQP X X X2200S4M14W1 008319-001 SS M25 EQP X X X2200A4N14W2 008320-001 AL 3/4 NPT EQP X X X2200A4M14W2 008321-001 AL M25 EQP X X X2200S4N14W2 008322-001 SS 3/4 NPT EQP X X X2200S4M14W2 008323-001 SS M25 EQP X X X2200A4N15W1 008324-XXX AL 3/4 NPT Pulse/Relay X X X2200A4M15W1 008325-XXX AL M25 Pulse/Relay X X X2200S4N15W1 008326-XXX SS 3/4 NPT Pulse/Relay X X X2200S4M15W1 008327-XXX SS M25 Pulse/Relay X X X2200A4N15W2 008328-XXX AL 3/4 NPT Pulse/Relay X X X2200A4M15W2 008329-XXX AL M25 Pulse/Relay X X X2200S4N15W2 008330-XXX SS 3/4 NPT Pulse/Relay X X X2200S4M15W2 008331-XXX SS M25 Pulse/Relay X X X2200A4N24W1 008356-001 AL 3/4 NPT Eagle Quantum X X X2200A4M24W1 008357-001 AL M25 Eagle Quantum X X X2200S4N24W1 008358-001 SS 3/4 NPT Eagle Quantum X X X2200S4M24W1 008359-001 SS M25 Eagle Quantum X X X2200A4N24W2 008360-001 AL 3/4 NPT Eagle Quantum X X X2200A4M24W2 008361-001 AL M25 Eagle Quantum X X X2200S4N24W2 008362-001 SS 3/4 NPT Eagle Quantum X X X2200S4M24W2 008363-001 SS M25 Eagle Quantum X X Ship Weight: Aluminum = 7lb (3.2kg) Stainless Steel = 14.6lb (6.7kg) *The last 3 digits of the part number identify the software configuration. Please see table D1 to choose the correct option. The EQ and EQP detectors are completely configurable using the configuration software and are shipped defaulted to the -001 setting. X2200M UV Flame Detector - Moly The X2200M UV detector utilizes a molybdenum (moly) sensing element. Moly-based sensors have an increased spectral range of 1850 to 2650 angstroms, which is better suited for detecting substances with unusual chemistry, sulfur fires, and some black powders. Model Part Number * Material Threads Output Div/Zone Ex d e Div/Zone Ex d FM/CSA/ ATEX/IECEx X2200MA4N13W1 008340-013 AL 3/4 NPT Relay/0-20 mA X X X2200MA4M13W1 008341-013 AL M25 Relay/0-20 mA X X X2200MS4N13W1 008342-013 SS 3/4 NPT Relay/0-20 mA X X X2200MS4M13W1 008343-013 SS M25 Relay/0-20 mA X X X2200MA4N13W2 008344-013 AL 3/4 NPT Relay/0-20 mA X X X2200MA4M13W2 008345-013 AL M25 Relay/0-20 mA X X X2200MS4N13W2 008346-013 SS 3/4 NPT Relay/0-20 mA X X X2200MS4M13W2 008347-013 SS M25 Relay/0-20 mA X X X2200MA4N14W1 008372-001 AL 3/4 NPT EQP X X X2200MA4M14W1 008373-001 AL M25 EQP X X X2200MS4N14W1 008374-001 SS 3/4 NPT EQP X X X2200MS4M14W1 008375-001 SS M25 EQP X X X2200MA4N14W2 008376-001 AL 3/4 NPT EQP X X X2200MA4M14W2 008377-001 AL M25 EQP X X X2200MS4N14W2 008378-001 SS 3/4 NPT EQP X X X2200MS4M14W2 008379-001 SS M25 EQP X X X2200MA4N15W1 008348-013 AL 3/4 NPT Pulse/Relay X X X2200MA4M15W1 008349-013 AL M25 Pulse/Relay X X X2200MS4N15W1 008350-013 SS 3/4 NPT Pulse/Relay X X X2200MS4M15W1 008351-013 SS M25 Pulse/Relay X X X2200MA4N15W2 008352-013 AL 3/4 NPT Pulse/Relay X X X2200MA4M15W2 008353-013 AL M25 Pulse/Relay X X X2200MS4N15W2 008354-013 SS 3/4 NPT Pulse/Relay X X X2200MS4M15W2 008355-013 SS M25 Pulse/Relay X X Ship Weight: Aluminum = 7lb (3.2kg) Stainless Steel = 14.6lb (6.7kg) *The last 3 digits of the part number identify the software configuration. Please see table D1 to choose the correct option. The EQP detectors are completely configurable using the S3 configuration software and are shipped defaulted to the -001 setting. X2200G UV Flame Detector - ATEX/IECEx/EN 54-10 The X2200G UV Flame Detector contains a Kr-85 free source tube. There are no differences in detection performance when compared to an X2200. Model Part Number * Material Threads Output Div/Zone Ex d e Div/Zone Ex d ATEX/IECEx/ EN 54-10 X2200GA4N11E1 013010-XXX AL 3/4 NPT Relay X X X2200GA4M11E1 013011-XXX AL M25 Relay X X X2200GS4N11E1 013012-XXX SS 3/4 NPT Relay X X X2200GS4M11E1 013013-XXX SS M25 Relay X X X2200GA4N11E2 013014-XXX AL 3/4 NPT Relay X X X2200GA4M11E2 013015-XXX AL M25 Relay X X X2200GS4N11E2 013016-XXX SS 3/4 NPT Relay X X X2200GS4M11E2 013017-XXX SS M25 Relay X X X2200GA4N13E1 013018-XXX AL 3/4 NPT Relay/0-20 mA X X X2200GA4M13E1 013019-XXX AL M25 Relay/0-20 mA X X X2200GS4N13E1 013020-XXX SS 3/4 NPT Relay/0-20 mA X X X2200GS4M13E1 013021-XXX SS M25 Relay/0-20 mA X X X2200GA4N13E2 013022-XXX AL 3/4 NPT Relay/0-20 mA X X X2200GA4M13E2 013023-XXX AL M25 Relay/0-20 mA X X X2200GS4N13E2 013024-XXX SS 3/4 NPT Relay/0-20 mA X X X2200GS4M13E2 013025-XXX SS M25 Relay/0-20 mA X X X2200GA4N23E1 013026-XXX AL 3/4 NPT Rly/0-20/HART X X X2200GA4M23E1 013027-XXX AL M25 Rly/0-20/HART X X X2200GS4N23E1 013028-XXX SS 3/4 NPT Rly/0-20/HART X X X2200GS4M23E1 013029-XXX SS M25 Rly/0-20/HART X X X2200GA4N23E2 013030-XXX AL 3/4 NPT Rly/0-20/HART X X X2200GA4M23E2 013031-XXX AL M25 Rly/0-20/HART X X X2200GS4N23E2 013032-XXX SS 3/4 NPT Rly/0-20/HART X X X2200GS4M23E2 013033-XXX SS M25 Rly/0-20/HART X X X2200GA4N14E1 013034-XXX AL 3/4 NPT EQP X X X2200GA4M14E1 013035-XXX AL M25 EQP X X X2200GS4N14E1 013036-XXX SS 3/4 NPT EQP X X X2200GS4M14E1 013037-XXX SS M25 EQP X X X2200GA4N14E2 013038-XXX AL 3/4 NPT EQP X X X2200GA4M14E2 013039-XXX AL M25 EQP X X X2200GS4N14E2 013040-XXX SS 3/4 NPT EQP X X X2200GS4M14E2 013041-XXX SS M25 EQP X X Ship Weight: Aluminum = 7lb (3.2kg) Stainless Steel = 14.6lb (6.7kg) *The last 3 digits of the part number identify the software configuration. Please see table D1 to choose the correct option. The EQP detectors are completely configurable using the configuration software and are shipped defaulted to the -001 setting. X2200G UV Flame Detector - CSA Model Part Number * Material Threads Output Div/Zone Ex d e Div/Zone Ex d CSA X2200GA4N13C1 013098-001 AL 3/4 NPT Relay and 0-20 mA X X X2200GA4N13C2 013102-001 AL 3/4 NPT Relay and 0-20 mA X X Ship Weight: Aluminum = 7lb (3.2kg) Stainless Steel = 14.6lb (6.7kg) X2200GM UV Flame Detector - Moly In addition to having a Kr-85 free source tube, the X2200GM UV Flame Detector utilizes a molybdenum (moly) sensing element. Moly-based sensors have an increased spectral range of 1850 to 2650 angstroms, which is better suited for detecting substances with unusual chemistry, sulfur fires, and some black powders. Model Part Number * Material Threads Output Div/Zone Ex d e Div/Zone Ex d FM/CSA/ ATEX/IECEx X2200GMA4N11E2 013042-003 AL 3/4 NPT Relay/0-20 mA X X2200GMA4N11E2 013042-013 AL 3/4 NPT Relay/0-20 mA X X2200GMA4M11E2 013043-003 AL M25 Relay/0-20 mA X X2200GMA4M11E2 013043-013 AL M25 Relay/0-20 mA X Ship Weight: Aluminum = 7lb (3.2kg) Stainless Steel = 14.6lb (6.7kg) *The last 3 digits of the part number identify the software configuration. Please see table D1 to choose the correct option. The EQP detectors are completely configurable using the S3 configuration software and are shipped defaulted to the -001 setting. X2200 UV Flame Detector / xWatch Camera Model Part Number * Material Threads Output Video FM/CSA X2200A3N33A2 009564-XXX AL 3/4 NPT Relay/0-20 NTSC X X2200A3M33A2 009565-XXX AL M25 Relay/0-20 NTSC X X2200S3N33A2 009566-XXX SS 3/4 NPT Relay/0-20 NTSC X X2200S3M33A2 009567-XXX SS M25 Relay/0-20 NTSC X X2200A3N43A2 009568-XXX AL 3/4 NPT Relay/0-20 PAL X X2200A3M43A2 009569-XXX AL M25 Relay/0-20 PAL X X2200S3N43A2 009570-XXX SS 3/4 NPT Relay/0-20 PAL X X2200S3M43A2 009571-XXX SS M25 Relay/0-20 PAL X X2200A3N34A2 009572-001 AL 3/4 NPT EQP NTSC X X2200A3M34A2 009573-001 AL M25 EQP NTSC X X2200S3N34A2 009574-001 SS 3/4 NPT EQP NTSC X X2200S3M34A2 009575-001 SS M25 EQP NTSC X X2200A3N44A2 009576-001 AL 3/4 NPT EQP PAL X X2200A3M44A2 009577-001 AL M25 EQP PAL X X2200S3N44A2 009578-001 SS 3/4 NPT EQP PAL X X2200S3M44A2 009579-001 SS M25 EQP PAL X Ship Weight: Aluminum = 9lb (4.1kg) Stainless Steel = 17.6lb (7.9kg) *The last 3 digits of the part number identify the software configuration. Please see table D1 to choose the correct option. The standard EQP detectors are completely configurable using the S3 software and are defaulted to the -001 setting. NOTES: 3 year warranty excludes xWatch camera. Models listed above come with a 2.3 mm lens on the camera, which emulates the 90° field of view of the flame detector. See section Flame F for additional lens options. -
Spectrex SharpEye 40/40C-I Multispectrum Quad-Sense Flame Detector
The SharpEye 40/40C-I Multispectrum Quad-Sense flame detector is part of the leading, next generation SharpEye 40/40 series. Featuring enhanced performance, advanced long distance detection of hydrocarbon fires at up to 215 ft (65 m), fast detection in under five seconds, and strengthened reliability, the SharpEye 40/40C-I is based on proven triple infrared (IR3) technology, ensuring high sensitivity with superior immunity to false alarms and surely keeping a SharpEye on your safety. Features and benefits Multi-Spectrum Quad-Sense flame detector - integrating four infrared (IR) sensors to further improve differentiation of flame sources from non-flame background radiation. Advanced long distance detection of hydrocarbon-based fuel and gas fires at up to 215 ft (65 m) Fast detection, under five sec Proven false alarm immunity Unparalleled reliability - 150,000 hours MTBF Wide temperature range: -40 °F (-40 °C) to 167 °F (75 °C) Enhanced durability backed up by with three-year warranty Five sensitivity levels, adapting to any application Innovative IR Built-In-Test - continuously validating the optical integrity and the electronic circuitry Multiple output options for maximum compatibility with standard infrastructures Plug and play - factory calibrated for immediate use in any fire detection system Universal wiring option for fast ordering process Heated optic for impeccable performance in challenging environmental conditions Worldwide and regionally certified for hazardous areas Performance and reliability approved by recognizable certification bodies SIL3 compatible Internal log event recorder to analyze past events Applications Oil and gas onshore and offshore installations and pipelines Chemical and petrochemical plants Storage tank farms Aircraft hangars Power generation facilities Pharmaceutical industry Printing industry Warehouses Automotive industry Explosives and munitions Waste disposal facilities Light industrial Product Data Sheet -
Spectrex SharpEye 40/40D-L4B Ultra Fast UV/IR Flame Detector
The SharpEye 40/40D-L4B UV/IR flame detector is part of the leading, next generation SharpEye 40/40 series. Detects flames with a large variety of hazardous sources, such as hydrocarbon-based fuel and gas fires. Featuring ultra-fast detection in 20 msec with proven immunity to false alarms, integrating UV and IR optical sensors to ensure flawless performance to keep a SharpEye on your safety! Features and benefits Integrating ultraviolet (UV) and infrared (IR) optical sensors for detection of hydrocarbon-based fuel and gas fires. 20 msec ultra fast detection Proven false alarm immunity Unparalleled reliability - 150,000 hours MTBF Best in class temperature range: -76 °F (-60 °C) to 185 °F (85 °C) Worldwide and regionally certified for hazardous areas Performance and reliability approved by recognizable certification bodies SIL3 compatible Enhanced durability backed up with five-year warranty Smart field of view integrity test, allowing flawless operation Innovative UV & IR built-in test - continuously validating the optical integrity and the electronic circuitry Multiple output options for maximum compatibility with standard infrastructures Plug and play - factory calibrated for immediate use in any fire detection system Universal wiring option for fast ordering process Three sensitivity levels, adapting to any application Two mode heated optics for impeccable performance in challenging environmental conditions Internal log event recorder to analyze past events Applications Oil & gas onshore and offshore installations and pipelines Chemical and petrochemical plants Storage tank farms Fuel and gas processing and storage facilities Power generation Explosives and munitions Fertilizer plants Automotive industry Vehicle battery charging stations Hydroxyl production and storage Aerospace industry Waste management facilities Pharmaceutical industry Printing Hazardous materials storage areas Food processing Product Data Sheet
Reviews
There are no reviews yet.